Function modules
7.10 Connecting the motors in parallel
Counter-example:
The gear ratios used to couple the motors with the load are large and the backlash and
elasticity in the drive train are therefore high. If the load then causes one of the motors to
rotate, but the other is still stationary, the drive without an encoder will stall.
If a motor is defective, the individual motor will be shut down on overcurrent by the motor
circuit breaker. The power unit will be shut down by the control (if available) or, in the case of
a turn-to-turn fault in the motor, the power unit will switch to fault status. The motor must then
be decoupled from the parallel grouping. Parameter p0306 is changed by the DDS/MDS
switchover.
Overview of important parameters (see SINAMICS S120/S150 List Manual)
● p0306[0...n] Number of motors in parallel connection
● p0307[0...n] Rated motor power
● p0640[0...n] Current limit
● p2002 Reference current
320
Function Manual, (FH1), 10/2008, 6SL3097-2AB00-0BP5