Safety Integrated basic functions
9.8 Commissioning the "STO", "SBC" and "SS1" functions
Acknowledging the safety faults
Faults associated with Safety Integrated Basic Functions must be acknowledged as follows:
1. Remove the cause of the fault.
2. Deselect "Safe Torque Off" (STO).
3. Acknowledge the fault.
If safety commissioning mode is exited when the safety functions are switched off (p0010 =
value not equal to 95 when p9601 = p9801 = 0), all the safety faults can be acknowledged.
Once safety commissioning mode has been selected again (p0010 = 95), all the faults that
were previously present reappear.
NOTICE
Safety faults can also be acknowledged (as with all other faults) by switching the drive unit
off and then on again (POWER ON).
If this action has not eliminated the fault cause, the fault is displayed again immediately
after power up.
Description of faults and alarms
Note
The faults and alarms for SINAMICS Safety Integrated are described in the following
documentation:
References: /LH1/ SINAMICS S120/S150 List Manual
388
Function Manual, (FH1), 10/2008, 6SL3097-2AB00-0BP5