12-pulse parallel connection of Basic Line Modules
With the 12-pulse variant of parallel connection, up to four Basic Line Modules on the line
side are supplied by one three-winding transformer. An even number of Basic Line Modules,
i.e two or four, must be divided equally between the two secondary windings. The Basic Line
Modules of both subsystems are controlled by a common Control Unit - even though the
input voltages are 30° out of phase.
There is also the redundant variant with which two BLMs in each case are controlled by one
Control Unit.
Figure 7-25
Figure 7-26
Drive functions
Function Manual, (FH1), 10/2008, 6SL3097-2AB00-0BP5
Parallel connection BLM 12-pulse single
Parallel connection BLM 12-pulse redundant
7.11 Parallel connection of power units
-
+
-
+
Function modules
327