Active Infeed open-loop control

Description
The Active Line Module can be controlled via the BICO interconnection by means of
terminals or the field bus. The operating status is indicated on the operating display r0002.
The missing enable signals for operation (r0002 = 00) are mapped in parameter r0046. The
EP terminals (enable pulses) must be connected in accordance with the Equipment Manual.
The drive unit must have been commissioned for the first time.
Acknowledge error
Errors that are still present but the causes of which have been rectified can be
acknowledged by means of a 0/1 edge at the "Acknowledge error" (p2103) signal.
Switching on the Active Line Module:
Figure 1-3
Drive functions
Function Manual, (FH1), 10/2008, 6SL3097-2AB00-0BP5
Active Infeed power-up
Infeed
1.1 Active Infeed