Exchanging a SINAMICS Sensor Module Integrated

The motor and encoder data required for the operation of a motor with DRIVE-CLiQ are
stored in their as-delivered condition on the EEPROM of the SINAMICS Sensor Module
Integrated (DRIVE-CLiQ at the Motor). Therefore, no data must be entered for the
commissioning of motors with DRIVE-CLiQ.
NOTICE
The user is responsible for backing up the data of the Sensor Module Integrated. Data are
not backed up automatically, and you are therefore required to back up this data on the
CompactFlash card.
Back up the data of the SINAMICS Sensor Module Integrated on the CompactFlash card
after every topology modification.
When servicing is required, the relevant data can then be quickly copied to a new, empty
SMI which can be put into operation immediately.
NOTICE
When a defective SMI needs to be mechanically exchanged for an empty SMI (without
motor or encoder data), the replacement must always be carried out by a service
technician.
NOTICE
If the SMI data have not been backed up despite the guidance above, an attempt should
first be made to save the data (before the module is dismounted). As long as the SMI is still
capable of communicating, this is the simplest method of transferring the correct motor and
encoder data to an empty SMI.
Drive functions
Function Manual, (FH1), 10/2008, 6SL3097-2AB00-0BP5
Basic information about the drive system
12.8 Exchanging a SINAMICS Sensor Module Integrated