Siemens SINAMICS S120 Commissioning Manual page 38

Canopen interface
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Add infeed
1.12 SDO services
SDO Abort codes
Table 1- 8
SDO Abort codes
Abort code
Description
0503 0000h
Toggle bit not alternated
0504 0000h
SDO protocol timed out
0504 0001h
Client/server command specifier not valid or unknown
0504 0002h
Invalid block size (block mode only)
0504 0003h
Invalid sequence number (block mode only)
0504 0004h.
CRC error (block mode only)
0504 0005h
Out of memory
0601 0000h
Unsupported access to an object
0601 0001h
Attempt to read a write-only object
0601 0002h
Attempt to write a read-only object
0602 0000h
Object does not exist in the object dictionary
0604 0041h
Object cannot be mapped to the PDO
0604 0042h
The number and length of the objects to be mapped would exceed PDO length
0604 0043h
General parameter incompatibility reason
0604 0047h
General internal incompatibility in the device
0602 0000h
Object does not exist in the object dictionary
0604 0041h
Object cannot be mapped to the PDO
0604 0042h
The number and length of the objects to be mapped would exceed PDO length
0604 0043h
General parameter incompatibility reason
0604 0047h
General internal incompatibility in the device
0606 0000h
Access failed due to a hardware error
0607 0010h
Data type does not match, length of service parameter does not match.
0607 0012h
Data type does not match, length of service parameter too high.
0607 0013h
Data type does not match, length of service parameter too low.
0609 0011h
Subindex does not exist
0609 0030h
Value range of parameter exceeded (only for write access)
0609 0031h
Value of parameter written too high
0609 0032h
Value of parameter written too low
0609 0036h
Maximum value is less than minimum value
0800 0000h
General error
0800 0020h
Data cannot be transferred to or stored in the application
0800 0021h
Data cannot be transferred to or stored in the application because of local control
0800 0022h
Data cannot be transferred to or stored in the application because of the current device state.
0800 0023h
Object dictionary dynamic generation failed or no object dictionary is present (e.g. object dictionary is
generated from file and generation fails because of a file error).
38
Commissioning Manual, (IH2), V2.6, 10/2008 Edition, 6SL3097-2AA00-0BP3