Commissioning
3.4 Configuring the drive unit using the STARTER commissioning tool
Commissioning in ONLINE mode
Figure 3-15
Note
Once you have entered the channel assignments in ONLINE mode, confirm them in this
dialog box by choosing Activate (refer to diagram above).
You can also confirm them in the expert list in parameter p8741 by choosing 1 (see
screenshot below).
Operator steps, activate the channel distribution in the OFFLINE mode
1. In the project navigator, open the expert list for the Control Unit as follows: Control Unit >
2. Search for parameter p8741 for confirming the channel assignment and enter 1.
3. In parameter p8742, you can see how many channels are still available (max. 25).
90
Activating the channels
right-click > Expert > Expert list.
Figure 3-16
Confirm channel assignment
Commissioning Manual, (IH2), V2.6, 10/2008 Edition, 6SL3097-2AA00-0BP3
CANopen interface