SS1 (time- -controlled) with external stop
Caution
!
In order to achieve stop Category 1 according to EN 60204--1 using function "SS1
(time controlled) with external stop (SS1E)", the higher--level control must facilitate
a controlled shutdown at the same time.
Caution
!
During the delay time (p9652), for "SS1 (time--controlled) with external stop",
arbitrary axis motion caused by the position controller is possible.
Differences between "Safe Stop 1 with OFF3 and with external stop"
"SS1 with OFF3" and "SS1 with external stop" have the following differences:
S In order to activate "SS1 with external stop", additionally parameter p9653 must
be set = 1.
S When SS1 is selected, the drive is not braked along the OFF3 ramp, but after
the delay time has expired (p9652), only STO/SBC is automatically initiated.
4.4.3
Overview of important parameters
(see Chapter 8.2.2 "Description of parameters")
S p1135[0...n]
S p9652
S p9852
S r9772
S r9773
S r9774
S r9872
S p9653
© Siemens AG 2015 All Rights Reserved
SINUMERIK 840D sl/SINAMICS S120 SINUMERIK Safety Integrated (FBSI sl) - - 10.2015 Edition
OFF3 ramp--down time
SI Safe Stop 1 delay time (Control Unit)
SI Safe Stop 1 delay time (Motor Module)
SI status (Control Unit)
SI status (Control Unit + Motor Module)
SI status (group STO) / SI stat group STO
SI status (Motor Module)
SI Safe Stop 1 drive--based braking response (only for "SS1
(time controlled) without OFF3"
Safety Functions integrated in the drive
4.4 Safe Stop 1 (SS1, time controlled)
4-65