SINUMERIK 840D sl/SINAMICS S120 SINUMERIK Safety Integrated (FBSI sl) - - 10.2015 Edition
SI P2: Write task for parameter rejected
OFF2
IMMEDIATELY (POWER ON)
The write task for one or several Safety Integrated parameters on
monitoring channel 2 was rejected.
Note:
This fault does not result in a safety stop response.
Fault value (r0949, interpret decimal):
10:
An attempt was made to enable the STO function although this cannot
be supported.
11:
An attempt was made to enable the SBC function although this cannot
be supported.
13:
An attempt was made to enable the SS1 function although this cannot
be supported.
14:
An attempt was made to enable the safe motion monitoring with the
higher--level control although this cannot be supported.
15:
An attempt was made to enable the motion monitoring functions
integrated in the drive although these cannot be supported.
16:
An attempt was made to enable PROFIsafe communication, although
this cannot be supported or the version of the PROFIsafe driver is
different in both monitoring channels.
19:
An attempt was made to enable the pulse suppression delay for ESR,
although this cannot be supported.
See also: r9771 (SI common functions (Control Unit)), r9871
(SI common functions (Motor Module))
Re fault value = 10, 11, 13, 14, 15, 16, 19:
-- Check whether there are faults in the safety function alignment
between the two monitoring channels (F01655, F30655) and if
required, carry out diagnostics for the faults involved.
-- Use a Motor Module that supports the required function.
-- Upgrade the Motor Module software.
-- Upgrade the Control Unit software.
SI P2: Control Unit software incompatible
OFF2
IMMEDIATELY (POWER ON)
The existing Control Unit software does not support the safe drive--
integrated motion monitoring function.
Note:
This fault results in a STOP A that cannot be acknowledged.
Fault value (r0949, interpret decimal):
Only for internal Siemens troubleshooting.
Check whether there are faults in the safety function alignment
between the two monitoring channels (F01655, F30655) and if
required, carry out diagnostics for the faults involved.
10.3Safety messages for SINAMICS S120
Diagnostics
10-791