Description of Function Codes
Function
Code
P6-10
0: Decelerate to stop
•
After the stop command is enabled, the AC drive decreases the output frequency according to
the deceleration time and stops when the frequency decreases to zero.
1: Coast to stop
•
After the stop command is enabled, the AC drive immediately stops the output. The motor will
coast to stop based on the mechanical inertia.
Function
Code
P6-11
Initial frequency of stop DC braking
P6-12
P6-13
P6-14
Initial frequency of stop DC braking: During the process of decelerating to stop, the AC drive
•
starts DC braking when the running frequency is lower than the value set in P6-11.
Waiting time of stop DC braking: When the running frequency decreases to the initial
•
frequency of stop DC braking, the AC drive stops output for a certain period and then starts DC
braking. This prevents faults such as overcurrent caused due to DC braking at high speed.
Stop DC braking current: Ts parameter specifies the output current at DC braking and is a
•
percentage relative to the base value.
Stop DC braking time: This parameter specifies the holding time of DC braking. If it is set to 0,
•
DC braking is cancelled.
The stop DC braking process is shown in the following figure. Figure 5-13 Stop DC braking
process
Parameter Name
Stop mode
Parameter Name
Waiting time of stop DC braking
Stop DC braking current
Stop DC braking time
Setting Range
0: Decelerate to top
1: Coast to stop
Setting Range
0.00 Hz to maximum
frequency
0.0–36.0s
0%–100%
0.0–36.0s
122
PE6000 User Manual
Default
0
Default
0.00 Hz
0.0S
0%
0.0s