PE6000 User Manual
Figure 3-25 Function code setting for fixed length control
P4-04 = 27
(Length pulses
input)
DI5
P4-00 to P4-09
=28
(Length reset)
Note
In the fixed length control mode, the direction cannot be identified and only the length shall
be calculated based on the number of pulses.
Only DI5 can be allocated with the function "Length count input".
An automatic stop system can be implemented if the length reached signal output by the DO
is fed back to the AC drive input terminal with the stop function.
Figure 3-26 Common application example of the fixed length control function
PB-05
PB-07
PB-06
PB-05 = 11
PB-06 = 11
CME
COM
DI1
DI2
DI3
DI4
DI5
CME
35
Operation, Display and Application Examples
P5-00 to P5-05 = 10
(Length reached)
PB-06 = 0
PE6000
PB-05(Set length)
P0-02 = 1, P4-00 = 1
P4-01 = 3, P4-02 = 4
P4-11 = 2
P4-03 = 26, P4-04 = 27
PB-07(Number of
pulses per meter).
P5-04 = 10