Description of Function Codes
If the output current of the AC drive is equal to or less than the zero current detection level and
the duration exceeds the zero current detection delay time, the corresponding DO becomes ON.
The zero current detection is shown in the following figure.
Figure 5-21 Zero current detection
Output current
Zero current
detection level
P8-34
Zero current
detection signal
Output overcurrent threshold
P8-36
Output overcurrent detection
P8-37
If the output current of the AC drive is equal to or higher than the overcurrent threshold and the
duration exceeds the detection delay time, the corresponding DO becomes ON. The output
overcurrent detection function is shown in the following figure.
Figure 5-22 Output overcurrent detection
Setting Range
delay time
Setting Range
Zero current detection
delay time P8-35
Default
0.0% (no detection)
0.1%–300.0% (rated motor current)
Default
0.00–600.00s
138
PE6000 User Manual
Time
Time
200.0%
0.00s