Pioneer PE6000 Series User Manual page 136

Table of Contents

Advertisement

Description of Function Codes
During acceleration, if the running frequency is smaller than the value of P8-25, acceleration
time 2 is selected. If the running frequency is larger than the value of P8-25, acceleration time 1 is
selected.
During deceleration, if the running frequency is larger than the value of P8-26, deceleration
time 1 is selected. If the running frequency is smaller than the value of P8-26, deceleration time 2 is
selected.
Terminal JOG preferred
P8-27
Setting Range
It is used to set whether terminal JOG is preferred.
If terminal JOG is preferred, the AC drive switches to terminal JOG running state when there is
a terminal JOG command during the running process of the AC drive.
Frequency switchover point
between acceleration time 1
P8-28
and acceleration time 2
Frequency switchover point
between deceleration time 1
P8-29
and deceleration time 2
The frequency detection function is the same as FDT1 function. For details, refer to the
P8-25
P8-26
0
1
Setting Range
Setting Range
Default
Disabled
Default
0.00 Hz to maximum frequency
Default
0.0%–100.0% (FDT2 level)
136
PE6000 User Manual
0
Enabled
50.00 Hz
5.0%