PE6000 User Manual
Acceleration time 4
P8-07
Acceleration time 4
P8-08
The PE6000 provides a total of four groups of acceleration/deceleration time, that is, the
preceding three groups and the group defined by F0-17 and F0-18.
Definitions of four groups are completely the same. Please see the descriptions of P0-17 to
P0-18.
You can switch over between the four groups of acceleration/deceleration time through
different state combinations of DI terminals. For more details, see the descriptions of P4-01 to
P4-05.
P8-09
Jump frequency 2
P8-10
P8-11
If the set frequency is within the frequency jump range, the actual running frequency is the
jump frequency close to the set frequency. Setting the jump frequency helps to avoid the
mechanical resonance point of the load.
The PE6000 supports two jump frequencies. If both are set to 0, the frequency jump function is
disabled.
The principle of the jump frequencies and jump amplitude is shown in the following figure.
Figure5-14 Principle of the jump frequencies
Setting Range
Setting Range
Setting Range
Jump frequency 1
Setting Range
Setting Range
Jump frequency 3
Setting Range
0.00 Hz to maximum frequency
Default
0.0–6500.0s
Default
0.0–6500.0s
Default
0.00 Hz to maximum frequency
Default
0.00 Hz to maximum frequency
Default
0.00 Hz to maximum frequency
129
Description of Function Codes
20.0s
20.0s
0.00Hz
0.00Hz
0.00Hz