PE6000 User Manual
Function
Code
Frequency offset of auxiliary frequency
P0-21
This parameter is valid only when the frequency source is set to "X and Y operation". The final
frequency is obtained by adding the frequency offset set in this parameter to the X and Y operation
result
Function
Code
P0-22
It is used to set the resolution of all frequency-related parameters.
If the resolution is 0.1 Hz, the PE6000 can output up to 3200 Hz. If the resolution is 0.01 Hz, the
PE6000 can output up to 320.00 Hz.
Modifying this parameter will make the decimal places of all frequency-related parameters
change and corresponding frequency values change.
This parameter is not resumed when factory setting is resumed.
Function
Code
Retentive of digital setting frequency
P0-23
This parameter is valid only when the frequency source is digital setting.
If P0-23 is set to 0, the digital setting frequency value resumes to the value of P0-08 (Preset
frequency) after the AC drive stops. The modification by using keys
UP/DOWN function is cleared.
If P0-23 is set to 1, the digital setting frequency value is the set frequency at the moment when
the AC drive stops. The modification by using keys
function remains effective.
Function
Code
P0-24
Parameter Name
source for X and Y operation
Parameter Name
Frequency reference resolution
Parameter Name
upon power failure
Parameter Name
Output selection
0.00 Hz to maximum
frequency (P0-10)
Setting Range
1: 0.1Hz
2: 0.01Hz
Note
Setting Range
0: Not retentive
1: Retentive
and
Setting Range
0: Yes
1: No
87
Description of Function Codes
Setting Range
and
or the terminal
or the terminal UP/ DOWN
Default
0.00Hz
Default
2
Default
0
Default
0