Function
Code
P7-09
It is used to display the accumulative running time of the AC drive. After the accumulative
running time reaches the value set in P8-17, the terminal with the digital output function 12
becomes ON.
Function
Code
P7-10
P7-11
Number of decimal places for load speed
P7-12
P7-08,P7-10, P7-11 It is used for
If P7-08 is set to any non-zero number, the password protection function is enabled. After a
password has been set and taken effect, you must enter the correct password in order to
enter the menu. If the entered password is incorrect you cannot view or modify parameters.
If F7-08 is set to 00000, the previously set user password is cleared, and the password
protection function is disabled.
Ÿ
P7-10 = 1,starting the
Ÿ
P7-10 = 0, disable this
P7-12 is used to set the number of decimal places for load speed display. The following
gives an example to explain how to calculate the load speed:
Assume that P7-06 (Load speed display coefficient) is 2.000 and P7-12 is 2 (2 decimal
places). When the running frequency of the AC drive is 40.00 Hz, the load speed is 40.00
x2.000=80.00 (display of 2 decimal places).
If the AC drive is in the stop state, the load speed is the speed corresponding to the set
frequency, namely, "set load speed". If the set frequency is 50.00 Hz, the load speed in the stop
Parameter Name
Accumulative running time
Parameter Name
Countdown started for stop
Preset value for timing stop
display
passwords for timing stop
Timer, until the P7-11 countdown to 0
countdown timer
Setting Range
0–65535 h
Setting Range
0:Stop
1:Start
0-65535
0: 0 decimal place
1: 1 decimal place
2: 2 decimal places
3: 3 decimal places
.
.
127
Description of Function Codes
Default
Default
.
0h
0
0
0