PE6000 User Manual
Function
Parameter Name
Code
Voltage source for V/F
P3-13
Voltage digital setting
P3-14
for V/F separation
V/F separation is generally applicable to scenarios such as induction heating, inverse power
supply and motor torque control.
If V/F separated control is enabled, the output voltage can be set in P3-14 or by means of
analog, multi-reference, simple PLC, PID or communication. If you set the output voltage by means
of non-digital setting, 100% of the setting corresponds to the rated motor voltage. If a negative
percentage is set, its absolute value is used as the effective value.
0: Digital setting (F3-14)
The output voltage is set directly in F3-14.
1: AI1; 2: AI2; 3: Keyboard potentiometer
The output voltage is set by AI terminals.
4: Pulse setting (DI5)
The output voltage is set by pulses of the terminal DI5.
Pulse setting specification: voltage range 9–30 V, frequency range 0–100 kHz
5: Multi-reference
If the voltage source is multi-reference, parameters in group P4 and PC must be set to
determine the corresponding relationship between setting signal and setting voltage.
Ÿ
6: Simple PLC
If the voltage source is simple PLC mode, parameters in group FC must be set to determine the
setting output voltage.
7: PID
The output voltage is generated based on PID closed loop. For details, see the description of
PID in group PA.
0: Digital setting (F3-14)
1: AI1
2: AI2
3: Keyboard potentiometer
4: Pulse setting (DI5)
5: Multi-reference
separation
6: Simple PLC
7: PID
8: Communication setting 100.0%
corresponds to the rated motor voltage
(P1-02, P4-02, P5- 02, P6-02).
0 V to rated motor voltage
Description of Function Codes
Setting Range
99
Default
0
0 V