Basic settings
By turning the digital dial, you can read another parameter.
Press the SET key to show the setting again.
Press the SET key twice to show the next parameter.
Fig. 5-4: Setting the starting torque
NOTES
A too large setting will cause the motor to overheat, resulting in an over current trip (OL (over
current alarm) then E.OC1 (over current shutoff during acceleration)), thermal trip (E.THM
(Motor overload shutoff), and E.THT (Inverter overload shutoff)).
When an error (E.OC1) occurs, release the start command, and decrease the value 1% by
1%. (Refer to page 7-11.)
If the inverter still does not operate properly after the above measures, adjust the accelera-
tion/deceleration setting, activate the vector control function by Pr. 80 "Simple magnetic vec-
tor control" (refer to section 6.7.2.) and 81 "Number of motor poles" and activate the real
sensorless vector control by Pr. 800. The Pr. 0 setting is invalid under advanced magnetic
flux vector control, real sensorless vector control and vector control.
FR-A700 EC
Operation
Screen at powering on
The monitor display appears.
Press the PU/EXT key to choose the PU
operation mode.
Press the MODE key to choose the parameter
setting mode.
Turn the digital dial until P.0 (Pr. 0) appears.
Press the SET key to show the currently set value.
"6.0" (initial value is 6% for the 00038) appears.
Turn the digital dial to change it
to the setting value of "7.0".
Press the SET key to set.
Simple mode parameter list
Display
PU indication is lit.
The parameter number
read previously
appears.
The initial value differs
according to the
capacity.
Flicker ... Parameter setting complete!
I001099E
5 - 7