Parameter
6.22.3
Operation command source and speed command source during
communication operation (Pr. 338, Pr. 339, Pr. 550, Pr. 551)
When the inverter RS-485 terminals or communication option is used, the external operation
command and speed command can be made valid. Also, the control command source in the
PU operation mode can be selected.
Pr.
Name
No.
Communication
338
operation command
source
Communication speed
339
command source
NET mode operation
550
command source
selection
PU mode operation
551
command source
selection
The above parameters can be set whenever the communication option is connected. (Refer to
section 6.21.4.)
Pr 550 and Pr. 551 are always write-enabled.
Select the control source of the network operation mode (Pr. 550)
Either the inverter RS-485 terminals or communication option can be specified as the source of
control in network operation mode.
For example, set Pr. 550 to "1" when executing parameter write, start command or frequency
setting from the inverter RS-485 terminals in the network operation mode independently of
whether the communication option is connected or not.
NOTE
Since Pr. 550 = 9999 (Automatic recognition of the communication option) in the initial set-
ting, parameter write, start command and frequency setting cannot be executed by commu-
nication using the inverter RS-485 terminals when the communication option is fitted.
(Monitor and parameter read can be performed.)
FR-A700 EC
Initial
Setting
Description
Value
Range
Operation command source
0
communication
0
1
Operation command source external
0
Speed command source communication
Speed command source external (Fre-
quency setting from communication is
1
invalid, terminal 2 and 1 setting from
0
external is valid)
Speed command source external (Fre-
quency setting from communication is
2
valid, terminal 2 and 1 setting from exter-
nal is invalid)
0
Communication option valid
1
Inverter RS-485 terminal valid
Automatic recognition of the communi-
9999
cation option
9999
Normally, the RS-485 terminals are valid.
When the communication option is fitted,
the communication option is valid.
Select the inverter RS-485 terminals as
1
the PU operation mode control source.
Select the PU connector as the PU opera-
2
2
tion mode control source.
Select the USB connector as the PU
3
operation mode control source.
Selection of operation mode and operation location
Parameters referred to
Refer to
Section
28
Multi-speed input
6.10.3
compensation
selection
59
Remote function
6.10.4
selection
79
Operation mode
6.22.1
selection
6 - 429