Mitsubishi Electric FR-A700 Instruction Manual page 411

Frequency inverter
Hide thumbs Also See for FR-A700:
Table of Contents

Advertisement

Parameter
Utilizing or changing offline auto tuning data for use
The data measured in the offline auto tuning can be read and utilized or changed.
Set Pr. 71 according to the motor used.:
Motor
Mitsubishi standard motor,
Mitsubishi high efficiency motor
Mitsubishi constant-torque motor
Vector control dedicated motor
Other manufacturer's standard motor
Other manufacturer's constant-torque motor
Tab. 6-53: Motor selection
For other settings of Pr. 71, refer to section 6.12.2.
In the parameter setting mode, read the following parameters and set desired values.
Parameter
Tab. 6-54: Parameter setting ranges
NOTES
The display units of the motor constants read using Pr. 684 Tuning data unit switchover can
be changed. Note that parameter values can not be changed.
1
When "9999" is set in Pr. 90 to Pr. 94 , Mitsubishi motor (SF-JR, SF-HR,SF-JRCA, SF-HRCA)
constants are used.
As the motor constants measured in the offline auto tuning have been converted into internal
data (****), refer to the following setting example when making setting:
Setting example:
To slightly increase Pr. 90 value (5%)
When Pr. 90 is displayed as "2516", set 2642, i.e. 2516 × 1.05 = 2641.8, in Pr. 90.
(The value displayed has been converted into a value for internal use. Hence, simple addi-
tion of a given value to the displayed value has no significance.)
FR-A700 EC
Name
Motor excitation
82
current
90
Motor constant R1
91
Motor constant R2
92
Motor constant L1
93
Motor constant L2
94
Motor constant X
859
Torque current
Pr. 82,
Pr. 684
Pr. 455
0
01800 or less
0.01A
02160 or more
0.1A
Selection and protection of a motor
SF-JR
SF-JR 4P (1.5kW or less)
SF-HR
Others
SF-JRCA 4P,
SF-TH (constant torque)
SF-HRCA 4P
Others (SF-JRC, etc.)
SF-V5RU, SF-THY
Setting Range
Setting Increments
0–**** ,9999
0–**** ,9999
0–**** ,9999
0–**** ,9999
0–**** ,9999
0–**** ,9999
0–**** ,9999
Pr. 90,
Pr. 91,
Pr. 92,
Pr. 458
Pr. 459
Pr. 460
Internal data converted value
0.001Ω
0.001Ω
0.1mH
0.01mΩ
0.01mΩ
0.01mH
Pr. 71
4
24
44
4
14
54
14
34
4
14
Initial Value
1
9999
1
9999
1
9999
1
9999
1
9999
1
9999
1
9999
Pr. 93,
Pr. 94,
Pr. 859,
Pr. 461
Pr. 462
Pr. 860
0.1mH
0.1%
0.01A
0.01mH
0.01%
0.1A
6 - 231