Mitsubishi Electric FR-A700 Instruction Manual page 296

Frequency inverter
Hide thumbs Also See for FR-A700:
Table of Contents

Advertisement

Torque control by real sensorless vector control, vector control
Torque command by CC-Link communication (Pr. 804 = 3, 5, 6)
● Writing a value to Pr. 805 or Pr. 806 using the FR-A7NC (communication option) sets the
torque command value.
● When "3 or 5" is set in Pr.804, torque command can be set in remote resister RWw1 or
RWwC using the FR-A7NC (communication option).
● By setting "5, 6" in Pr.804, the range of torque command setting from FR-A7NC (communi-
cation option) is set from −327.68% to 327.67% (0.01% increments).
Pr. 804 Torque Command Source
1
3
5
6
Tab. 6-20: Torque command by CC-Link communication
NOTE
For details of the setting with the FR-A7NC, refer to the FR-A7NC instruction manual.
Torque command by 16 bit digital input (Pr. 804 = 4)
Give a torque command by 16 bit or 12 bit digital input using the FR-A7AX (plug-in option).
NOTE
For details of the setting with the FR-A7AX, refer to the FR-A7AX instruction manual.
Change the torque characteristics in the constant power (Pr. 803)
Due to the motor characteristics, torque is reduced at or above the base frequency. Set "1" in Pr.
803 "Constant power range torque characteristic selection" when you want to limit the torque to
be constant even at or above the base frequency.
Fig. 6-29: Motor characteristic
6 - 116
Torque command by parameter setting (Pr. 805 or Pr. 806)
Torque command by parameter setting (Pr. 805 or Pr. 806)
Torque command from remote resister (RWw1 or RWwC) with
using CC-Link communication (FR-A7NC)
Torque command by parameter setting (Pr. 805 or Pr. 806)
Torque command from remote resister (RWw1 or RWwC) with
using CC-Link communication (FR-A7NC)
Torque command by parameter setting (Pr. 805 or Pr. 806) without
using CC-Link communication (FR-A7NC)
Torque command by parameter setting (Pr. 805 or Pr. 806) with
using CC-Link communication (FR-A7NC)
Constant torque range
Constant power range
Base speed
Parameter
Setting Range
600 to 1400
(−400% to 400%)
600 to 1400
(−400% to 400%)
600 to 1400
(−400% to 400%)
−32768 to 32767
(two's complement)
(−327.68% to 327.67%)
600 to 1400
(−400% to 400%)
−32768 bis 32767
(two's complement)
(−327.68 % to 327.67%)
Pr. 803 = 1:
constant torque limit
Pr. 803 = 0:
constant power limit
(torque reduction)
Speed
Incre-
ments
1%
1%
1%
0.01%
1%
0.01%
I001526E

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-a740 ecFr-a700 ec

Table of Contents