Alarm Code Output Selection - Mitsubishi Electric FR-A700 Instruction Manual

Frequency inverter
Hide thumbs Also See for FR-A700:
Table of Contents

Advertisement

Parameter
6.17.2

Alarm code output selection

At alarm occurrence, its description can be output as a 4-bit digital signal from determined open
collector output terminals.
The alarm code can be read by a programmable controller, etc., and its corrective action can be
shown on a display, etc.
Pr.
Name
No.
Alarm code output
76
selection
By setting Pr. 76 to "1" or "2", the alarm code can be output to the output terminals.
When the setting is "2", an alarm code is output at only alarm occurrence, and during normal
operation, the terminals output the signals assigned to Pr. 190 to Pr. 196 "Output terminal func-
tion selection".
The following table indicates alarm codes to be output. (0: output transistor off, 1: output tran-
sistor on)
Operation Panel
Indication
FR-DU07
Normal
E.OC1
E.OC2
E.OC3
E.OV1
E.OV2
E.OV3
E.THM
E.THT
E.IPF
E.UVT
E.FIN
E.BE
E.GF
E.OHT
E.OLT
E.OPT
E.OP1
Other than the
above
Tab. 6-99: Alarm codes
When Pr. 76 = "2", the output terminals output the signals assigned to Pr. 190 to Pr. 196.
.
NOTE
When a value other than "0" is set in Pr. 76.
When an alarm occurs, the output terminals SU, IPF, OL, FU output the signal in the above
table, independently of the Pr. 190 to Pr. 196 "Output terminal function selection" settings.
Please be careful when inverter control setting has been made with the output signals of
Pr. 190 to Pr. 196.
FR-A700 EC
Initial
Setting
Description
Value
Range
0
Without alarm code output
1
With alarm code output
0
Alarm state: Alarm code output
2
No Alarm: Output of information
assigned with Parameter 190–196
SU
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
1
Operation setting at alarm occurrence
Output of Output Terminals
IPF
OL
0
0
0
0
0
1
0
1
1
0
1
0
1
1
1
1
0
0
0
0
0
1
0
1
1
0
1
0
1
1
1
1
1
1
Parameters referred to
190–196
Output terminal
function selection
Alarm Code
FU
0
1
0
1
0
1
0
1
0
1
0
A
1
B
0
C
1
D
0
E
0
E
1
Refer to
Section
6.14.5
0
1
2
3
4
5
6
7
8
9
F
6 - 355

Hide quick links: