Mitsubishi Electric FR-A700 Instruction Manual page 219

Frequency inverter
Hide thumbs Also See for FR-A700:
Table of Contents

Advertisement

Parameter
Parameter
Func-
Name
tion
Output phase failure
251
protection selection
Input phase failure
872
protection selection
252
Refer to Pr. 73
253
Life alarm status
255
display
Inrush current limit
256
circuit life display
Control circuit
257
capacitor life display
Main circuit capacitor
258
life display
Main circuit capacitor
259
life measuring
260
Refer to Pr. 72
Tab. 6-1:
Parameter overview (39)
FR-A700 EC
Incre-
Initial
Setting
ments
Value
Range
0
1
1
1
0
1
0
1
1
0
(0–15)
1%
100%
(0–100%)
1%
100%
(0–100%)
1%
100%
(0–100%)
1
0
0/1
Description
Without output phase failure
protection
With output phase failure
protection
Without input phase failure
protection
With input phase failure
protection
Display whether the control circuit
capacitor, main circuit capacitor,
cooling fan, and each parts of the
inrush current limit circuit has
reached the life alarm output level
or not.
Display the deterioration degree of
the inrush current limit circuit.
(Reading only)
Display the deterioration degree of
the control circuit capacitor.
(Reading only)
Display the deterioration degree of
the main circuit capacitor.
(Reading only)
The value measured by Pr. 259 is
displayed.
Setting "1" and turning the power
supply off starts the measurement
of the main circuit capacitor life.
When the Pr. 259 value is "3" after
powering on again, the measuring
is completed. Read the deteriora-
tion degree in Pr. 258.
Parameter overview
All
Para-
Para-
para-
meter
meter
meter
copy
clear
Refer
clear
to
page
✔: enabled
—: disabled
6-356
6-527
6 - 39