Mitsubishi Electric FR-A700 Instruction Manual page 58

Frequency inverter
Hide thumbs Also See for FR-A700:
Table of Contents

Advertisement

Control circuit specifications
Terminal
(Output volt-
10V DC)
(Output volt-
5V DC)
Tab. 3-6: Input signals (2)
3 - 20
Name
External transistor
common, contact
SD
input common
(sink)
24V DC
power supply,
PC
contact input
common
(source)
10E
age
Frequency setting
power supply
10
age
Frequency setting
2
(voltage)
Frequency setting
4
(current)
Description
A determined control function is activated, if
the corresponding terminal is connected to the
terminal SD (sink logic). The SD terminal is
isolated from the digital circuits via opto cou-
plers.
The terminal is isolated from the reference
potential of the analog circuit (terminal 5).
Common reference potential (0V) for 24V DC/
0.1A output (PC terminal).
24V DC/0.1A output
With negative logic and control via open col-
lector transistors (e.g. a PLC) the positive pole
of an external power source must be con-
nected to the PC terminal. With positive logic
the PC terminal is used as a common refer-
ence for the control inputs. This means that
when positive logic is selected (default setting
of the EC units) the corresponding control
function is activated by connecting its terminal
to the PC terminal.
When connecting the frequency setting poten-
tiometer at an initial status, connect it to termi-
nal 10.
Change the input specifications with Pr. 73
when connecting it to terminal
section 6.20.3.)
Recommended potentiometer: 1 kΩ, 2 W lin-
ear, multi turn potentiometer
Inputting 0 to 5VDC (or 0 to 10V, 0/4 to 20mA)
provides the maximum output frequency at 5V
(10V, 20mA) and makes input and output pro-
portional. Use Pr. 73 to switch from among
input 0 to 5VDC (initial setting), 0 to 10VDC,
and 0 to 20mA. Set the voltage/current input
switch in the ON position to select current
input (0 to 20mA).
Inputting 0/4 to 20mA DC (or 0 to 5V, 0 to 10V)
provides the maximum output frequency at
20mA (5V, 10V) makes input and output pro-
portional. This input signal is valid only when
the AU signal is on (terminal 2 input is invalid).
Use Pr. 267 to switch between the input 0 to
20mA (initial value) and 0 to 5V DC, 0 to 10V DC.
Set the voltage/current input switch in the OFF
position to select voltage input (0 to 5V/0 to 10V).
Use Pr. 858 to switch terminal functions.
Rated
Specifications
Power supply
voltage range:
19.2 to
28.8V DC
Current con-
sumption:
100mA
10V DC ± 0,4V,
Permissible
load current
10mA
10E.
(Refer to
5,2V DC ± 0,2V,
Permissible
load current
10mA
Voltage input:
Input resist-
ance:
10kΩ ± 1kΩ
Maximum
permissible
voltage:
20V DC
Current input:
Input resist-
ance:
245Ω ± 5Ω
(while power is
on)
Maximum
permissible
current: 30mA
Wiring
Refer to
3-25
6-369
6-369
6-369
6-369

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-a740 ecFr-a700 ec

Table of Contents