Mitsubishi Electric FR-A700 Instruction Manual page 676

Frequency inverter
Hide thumbs Also See for FR-A700:
Table of Contents

Advertisement

Special operation
Signal
FUP
FDN
RL
PID
SLEEP
SE
Tab. 6-169:I/O signals and parameter settings (2)
The half-tone screened areas indicate the parameter initial values.
For the setting method via LONWORKS communication, refer to the LONWORKS commu-
nication option (FR-A7NL) instruction manual.
For the setting method via CC-Link communication, refer to the CC-Link communication
option (FR-A7NC) instruction manual.
When "100" or larger value is set to any of Pr. 190 to Pr. 196 "Output terminal function
selection", the terminal output has sink logic. (Refer to section 6.14.5 for details.)
If Pr. 133 is used for the set point signal (setting ≠ 9999) any additional set point signal
applied to terminals 2-5 will be ignored.
NOTES
Changing the terminal function using any of Pr. 178 to Pr. 189, 190 to Pr. 196 may affect the
other functions. Please make setting after confirming the function of each terminal.
When the Pr. 73 and Pr. 267 settings were changed, check the voltage/current input switch
setting. Different setting may cause a fault, failure or malfunction. (Refer to page 6-372 for
setting.)
6 - 496
Terminal
Function
used
Upper limit
output
Lower limit
output
Forward
Depending
on
(reverse) rota-
Pr. 190–196
tion direction
output
During PID
control
activated
PID output
interruption
(SLEEP)
Output
SE
terminal
common
Description
Output to indicate that the meas-
ured value signal exceeded the
upper limit value (Pr. 131).
Output when the measured value
signal falls below the lower limit
(Pr.132).
"Hi" is output to indicate that the
output indication of the parameter
unit is forward rotation (FWD) or
"Low" to indicate that it is reverse
rotation (REV) or stop (STOP).
Turns on during PID control.
Turns on when the PID output
interruption function is performed.
Common terminal for terminals
FUP, FDN, RL, PID and SLEEP
Parameter
Parameter Setting
Pr. 128 = 20, 21, 60, 61
Pr. 131 ≠ 9999
Set "15" or "115" to any of
Pr. 190–Pr. 196 .
Pr. 128 = 20, 21, 60, 61
Pr. 132 ≠ 9999
Set "14" or "114" to any of
Pr. 190–Pr. 196.
Set "15" or "115" to any of
Pr. 190–Pr. 196.
Set "47" or "147" to any of
Pr. 190–Pr. 196.
Pr. 575 ≠ 9999
Set "70" or "170" to any of
Pr. 190–Pr. 196.