Output Terminal Function Selection (Pr. 190 To Pr. 196) - Mitsubishi Electric FR-A700 Instruction Manual

Frequency inverter
Hide thumbs Also See for FR-A700:
Table of Contents

Advertisement

Function assignment of external terminals
6.14.5

Output terminal function selection (Pr. 190 to Pr. 196)

You can change the functions of the open collector output terminal and relay output terminal.
Pr.
Name
No.
RUN terminal
190
function selection
SU terminal
191
function selection
Open
IPF terminal
collector
192
function selection
output
terminal
OL terminal
193
function selection
FU terminal
194
function selection
ABC1 terminal
195
function selection
Relay
output
ABC2 terminal
196
terminal
function selection
You can set the functions of the output terminals.
Refer to the following table and set the parameters:
0 to 99: Source logic
100 to 199: Sink logic
Setting
Terminal Function
Source
Sink
Logic
Logic
0
100
RUN
1
101
SU
2
102
IPF
3
103
OL
4
104
FU
5
105
FU2
6
106
FU3
Tab. 6-86:
Output terminal function assignment (1)
6 - 298
Initial
Initial Signal
Value
0
RUN (inverter running)
1
SU (up to frequency)
IPF (instantaneous power
2
failure, under voltage)
3
OL (overload alarm)
FU (output frequency
4
detection)
99
ALM (alarm output)
9999
No function
Inverter running
Up to frequency
Instantaneous power failure/
under voltage
Overload alarm
Output frequency detection
Second output frequency
detection
Third output frequency detection
Setting Range
Parameters referred to
0–8/10–20/25–28/
30–36/39/41–47/
64/70/84/85/90–99/
100–108/110–116/
120/125–128/
130–136/139/
141–147/164/170/
184/185/190–199/
9999
0–8/10–20/25–28/
30–36/39/41–47/
64/70/84/85/90/91/
94–99/100–108/
110–116/120/
125–128/130–136/
139/141–147/
164/170/184/185/
190/191/194–199/
9999
Operation
Output during operation when
the inverter output frequency
rises to or above Pr. 13
"Starting frequency".
Output when the output fre-
quency is reached to the set
frequency.
Output at occurrence of an
instantaneous power failure
or when under voltage protec-
tion is activated.
Output while stall prevention
function is activated.
Output when the output
frequency reaches the
frequency setting in Pr. 42
(Pr. 43 for reverse rotation).
Output when the output fre-
quency reaches the fre-
quency setting in Pr. 50.
Output when the output fre-
quency reaches the fre-
quency set in Pr. 116
Parameter
Refer to
Section
13
Starting
6.11.2
frequency
76
Alarm code
6.17.2
output selection
Related Parame-
Refer to
ters
Page
6-303
Pr. 41
6-309
Pr. 57
6-337
Pr. 22, Pr. 23,
Pr. 66, Pr. 148,
6-155
Pr. 149, Pr. 154
Pr. 42, Pr. 43
6-309
Pr. 50
Pr. 116