Operation selection at power failure
Power failure stop mode (Pr. 261 = 1 or 11)
If power is restored during power failure deceleration, deceleration to a stop is continued and the
inverter remains stopped. To restart, turn off the start signal once, then turn it on again.
Fig. 6-165: Power restoration
When automatic restart after instantaneous power failure is selected (Pr. 57 ≠ 9999), decel-
NOTES
eration to stop function is invalid and the restart after instantaneous power failure operation
is performed.
After a power failure stop, the inverter will not start if the power supply is switched on with
the start signal (STF/STR) input. After switching on the power supply, turn off the start signal
once and then on again to make a start.
Fig. 6-166: Restart at power restoration
6 - 348
Pr. 261 = 1
Power
supply
Output
frequency
Time
Power
supply
Not started as inverter is
stopped due to power
failure
During deceleration at
occurrence of power failure
During stop at
occurrence of
power failure
Turn off STF once to make
acceleration again
ON
Output
frequency
OFF
ON
Parameter
I001174E
I001175E