Servo control
4.13 Motor data identification
Parameters to control the motor data identification
The following parameters influence the motor data identification:
Table 4- 11
Static measurement (motor data identification)
The setting of p1959 has the following effects for the direction of rotation p1821:
1)
- Positive direction permitted, with setting p1821=0 means: Clockwise direction of rotation
- Negative direction permitted, with setting p1821=1 means: Counter-clockwise direction of rotation
Note
If a brake is being used and is operational (p1215 = 1, 3), the stationary measurement is
made with closed brake. If possible (e.g. no hanging/suspended axis), we recommend that
the brake is opened before the motor data identification (p1215 = 2). This also means that
the encoder size can be adjusted and the commutation angle calibrated.
152
Parameters for control
p0640 current limit
p1215 motor holding brake configuration
p1909 motor data identification control word
p1910 motor data identification, stationary
p1959.14/.15 positive/negative direction per-
mitted
1)
Rotating measurement
p0640 current limit
p1082 maximum speed
p1958 motor data identification ramp-
up/ramp-down time
p1959 rotating measurement configuration
p1960 rotating measurement selection
Function Manual, 11/2017, 6SL3097-4AB00-0BP5