● OFF3
– Switch to speed-controlled operation
– n_set = 0 is input immediately to brake the drive along the OFF3 deceleration ramp
– When standstill is detected, the motor brake (if parameterized) is closed.
– The pulses are suppressed when the motor brake application time (p1217) has
– Switching-on inhibited is activated.
Parameterization with STARTER
The "Torque setpoint" parameter screen is selected with the
STARTER commissioning tool.
Function diagrams (see SINAMICS S120/S150 List Manual)
• 5060
• 5610
Overview of important parameters (see SINAMICS S120/S150 List Manual)
• p1300[0...n]
• r1406.8...12
• p1501[0...n]
• p1511[0...n]
• p1512[0...n]
• p1513[0...n]
• r1515
Drive functions
Function Manual, 11/2017, 6SL3097-4AB00-0BP5
(p1135).
elapsed. Standstill is detected when the actual speed value is less than the speed
threshold (p1226) or when the monitoring time (p1227) that started when speed
setpoint ≤ speed threshold (p1226) has expired.
Servo control - Torque setpoint, switchover control mode
Servo control – torque limiting/reduction, interpolator
Open-loop/closed-loop control operating mode
CO/BO: Control word, speed controller
BI: Change over between closed-loop speed/torque control
CI: Supplementary torque 1
CI: Supplementary torque 1 scaling
CI: Supplementary torque 2
Supplementary torque total
Servo control
4.4 Speed controller
icon in the toolbar of the
97