Figure 16-2 Layout

16.2 (Optional) Installing an In-Room Access Actuator

Context
Procedure
Step 1 Take out the waterproof box and remove its cover.
Issue 02 (2018-03-31)
The BOM number of an access actuator is 52271874.
It is recommended that the access actuator be installed 0.5 m away from the door edge
and 2.2 m above the floor at the inner side of a door.
The communication distance (network cable length) between the access actuator and the
access control device should not exceed 5 m. If the distance exceeds 5 m, prepare the cable
onsite.
Before installing the access actuator, install a cable trough or drill a cable hole in the wall,
and route the lead into the trough or hole.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
16 (Optional) Installing In-Room Access Control
Devices and Cameras
246