FusionModule2000 Smart Modular Data Center
Installation Guide
Battery Short Circuit
Battery short circuits may cause personal injury. The high transient current generated by a
short circuit may release a surge of power and cause fire.
To avoid battery short circuits, do not replace batteries online.
Harmful Gas
Do not use unsealed lead-acid batteries. Place and secure lead-acid batteries horizontally to
prevent inflammation or device corrosion due to flammable gas emitted from batteries.
Lead-acid batteries emit flammable gas when used. Therefore, store these batteries in
well-ventilated areas, and take fire-prevention measures.
Battery Temperature
High temperatures may result in battery distortion, damage, and electrolyte overflow.
When the battery temperature is higher than 60° C, check the battery for electrolyte overflow.
If the electrolyte overflows, handle the leakage immediately.
Electrolyte Leakage
When the electrolyte leaks, absorb and neutralize the electrolyte immediately.
When moving or handling a battery whose electrolyte leaks, note that the leaked electrolyte
may hurt human bodies. If the electrolyte leaks, immediately use the following substances to
neutralize and absorb the leaked electrolyte:
Issue 02 (2018-03-31)
When handling a battery, ensure that its electrodes are upward. Placing the battery upside
down or tilting the battery is prohibited.
Switch off the power supply during installation and maintenance.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
1 Safety Precautions