FusionModule2000 Smart Modular Data Center
Installation Guide
Step 5 Sign on the Packing List with the customer after verifying that all required items are
delivered.
Step 6 Store the items properly.
----End
Follow-up Procedure

2.3 Installation Environment Check

Ensure that the installation environment meets the requirements before installation.
Table 2-1 Installation environment checklist
Check Item
Floor load bearing
capacity
Equipment room net
height
Device passage and
door height and
width
Issue 02 (2018-03-31)
Put the items to be installed immediately onto an ESD surface, such as a polyethylene
(PE) bag or an expandable polyethylene (EPE) foam.
Pack the items not to be installed immediately with their original packing materials. Put
them in a dry and cool environment without exposure to sunlight or sources of strong
electromagnetic radiation.
Criteria
Standard live load of the main
equipment room: 8–12 kN/m
battery cabinet is placed inside the
module, use the standard live load of
the main equipment room as a
reference.)
Suspended load of the main
equipment room: 1.2 kN/m
Standard live load of the
uninterruptible power system (UPS)
room: 8–10 kN/m
Standard live load of the battery
room: 16 kN/m
Standard live load of the monitoring
center: 6 kN/m
2000 mm high cabinets (without
bases): > 2800 mm
2200 mm high cabinets (without
bases): > 3000 mm
NOTICE
Equipment room net height (with bases) =
Equipment room net height (without bases)
+ Base height
Height ≥ 2.2 m and width ≥ 1.2 m (If a
2200 mm high cabinet cannot go
through, tilt the cabinet.)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
2
(If the
2
2
2
2
2 Installation Preparations
Check Result
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
10