Huawei FusionModule2000 Installation Manual page 43

Smart modular data center
Hide thumbs Also See for FusionModule2000:
Table of Contents

Advertisement

FusionModule2000 Smart Modular Data Center
Installation Guide
Figure 3-10 Column in the aisle containment (A < 800 mm)
Issue 02 (2018-03-31)
Cabinet places on the column side are left blank and sealed by sealing plates. Directions of the
concave sides of the sealing plates are shown in
Install cable trays over the cabinets on both sides of the blank cabinet places for routing
strong-current and weak-current cables.
Install an adjustable skylight over the aisle containment. The area to be covered by the adjustable
skylight is shown in
Figure
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Figure
3-10.
3 Smart Module Layout Requirements
3-10.
34

Advertisement

Table of Contents
loading

Table of Contents