Figure 10-32 Assembling a door frame
Stand the door frame, and partially secure left and right posts to the skylight connective
plate using four M6x16 screws, flat washers, and nuts, as shown by (1) in
Secure the left and right posts to the cabinet using four M6x16 screws, as shown by (2)
in
Figure
10-33.
Select the posts and cabinet fixing holes based on the cabinet height.
Before tightening the screws, remove the clips and set them aside to facilitate installation. After
tightening the screws, reinstall the clips on the posts.
Verify that the posts are flush with the cabinet frame.
Measure the levelness of the upper frame mounting kit using a level. If the levelness is
greater than or equal to 0.5° , adjust the cabinet anchor bolts to level the upper frame
mounting kit.
Tighten the four M6x16 screws and nuts to secure the left and right posts to the skylight
connective plates.
Reinstall the post side panels, as shown by (3) in
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
10 Installing the Aisle Containment
Figure
10-33.
Figure
10-33.
123