FusionModule2000 Smart Modular Data Center
Installation Guide
Figure 3-5 Column occupying part of a cabinet place (A < 800 mm and B ≥ 400 mm)
Issue 02 (2018-03-31)
Cabinet places on both sides of the column are left blank and sealed by sealing plates. Directions of
the concave sides of the sealing plates are shown in
Install cable trays over the cabinets on both sides of the blank cabinet places for routing
strong-current and weak-current cables.
Install an adjustable skylight over the aisle containment. The area to be covered by the adjustable
skylight is shown in
Figure
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Figure
3-5.
3 Smart Module Layout Requirements
3-5.
29