IndraDrive Mi Drive Systems with KCU02, KSM02,
KMS02/03, KMV03, KNK03, KLC03
supply (P
= power dissipation which KCU generates by converting the
Diss_cont
24 V voltage to 42 V; depends on the load at the 42V supply.).
Configure the 24V supply for the power consumption of KCU and
the load-dependent inrush current.
Take into account that other loads (e.g. HMV, HCS) are operated
at the same 24V supply.
KCU output X53 load:
P
KCU load at X53
42V
f
1.3 (correction factor for losses on the hybrid cable)
cable
n
Number of KSM/KMS without holding brake
m
Number of KSM/KMS with holding brake
P
KSM/KMS power consumption
N3
Fig. 7-4:
Load X53
KCU power consumption from 24V supply:
P
KCU power consumption
N3 (KCU)
f
1.2 (correction factor for KCU power supply unit losses)
SMPS
P
KCU load at X53
42V
Fig. 7-5:
KCU power consumption from 24V supply
The 24V supply has to make available the inrush current
generated when each KCU drive connection box is switched on.
The inrush current depends on the power consumption P
(see calculation above):
P
≤ 288 W
N3(KCU)
Inrush current I
288 W < P
Inrush current I
The holding brakes integrated in KSM have no effect on the
inrush current of KCU.
Notes on project planning
= 10 A
N3_EIN
N3(KCU)
= P
/U
N3_EIN
N3(KCU)
N3