IndraDrive Mi Drive Systems with KCU02, KSM02,
KMS02/03, KMV03, KNK03, KLC03
Install the covers and guards provided for this purpose before switching
on.
Never touch any electrical connection points of the components while
power is turned on.
Do not remove or plug in connectors when the component has been
powered.
Under specific conditions, electric drive systems can be operated at
mains protected by residual-current-operated circuit-breakers sensitive
to universal current (RCDs/RCMs).
Secure built-in devices from penetrating foreign objects and water, as
well as from direct contact, by providing an external housing, for
example a control cabinet.
High housing voltage and high leakage current! Danger to life, risk of injury
by electric shock!
Before switching on and before commissioning, ground or connect the
components of the electric drive and control system to the equipment
grounding conductor at the grounding points.
Connect the equipment grounding conductor of the components of the
electric drive and control system permanently to the main power supply
at all times. The leakage current is greater than 3.5 mA.
Establish an equipment grounding connection with a minimum cross
section according to the table below. With an outer conductor cross
section smaller than 10 mm
equipment grounding conductors is allowed, each having the same
cross section as the outer conductors.
Cross section outer
conductor
1.5 mm
2
(16 AWG)
2.5 mm
2
(14 AWG)
4 mm
2
(12 AWG)
6 mm
(10 AWG)
2
10 mm
2
(8 AWG)
16 mm
2
(6 AWG)
25 mm
(4 AWG)
2
35 mm
2
(2 AWG)
50 mm
(1/0 AWG)
2
70 mm
2
(2/0 AWG)
...
Tab. 3-1:
Minimum cross section of the equipment grounding connection
Safety instructions for electric drives and controls
(8 AWG), the alternative connection of two
2
Minimum cross section equipment grounding conductor
Leakage current ≥ 3.5 mA
1 equipment grounding
conductor
10 mm
2
(8 AWG)
16 mm
(6 AWG)
2
25 mm
(4 AWG)
2
35 mm
2
(2 AWG)
...
R911335703_Edition 04 Bosch Rexroth AG
39/407
2 equipment grounding
conductors
2 × 1.5 mm
2
(16 AWG)
2 × 2.5 mm
2
(14 AWG)
2 × 4 mm
2
(12 AWG)
2 × 6 mm
(10 AWG)