Bosch rexroth IndraDrive Mi KCU02 Project Planning Manual page 325

Drive systems
Hide thumbs Also See for rexroth IndraDrive Mi KCU02:
Table of Contents

Advertisement

IndraDrive Mi Drive Systems with KCU02, KSM02,
KMS02/03, KMV03, KNK03, KLC03
Mounting
Installation
The accessory is screwed to the equipment grounding conductor connections
of HCS01 (M5, tightening torque: 5 Nm)
Fig. 10-9:
HAS05.1-023, dimensions, mounting screws
Connection
Significance
Equipment grounding conductors can be directly connected to
the accessory (screw: M5; tightening torque: 5 Nm).
Hybrid cable shield (RKH0341, RKH0441, RKH0541,
RKH0909)
X52
Status messages; hybrid cable connection
X52.1
Status messages; HCS01 connection (X47, X49)
X53
Control voltage; hybrid cable connection
X53.1
Control voltage; 42 V power supply unit connection
Suitable power supply units:
PULS CPS20.361
(input voltage: AC 100 ... 240 V)
PULS QT20.361
(input voltage: AC 380 ... 480 V)
Tab. 10-4:
Connection points
Accessories
R911335703_Edition 04 Bosch Rexroth AG
311/407