ABB RMC-100 User Manual page 134

Remote modular controller
Hide thumbs Also See for RMC-100:
Table of Contents

Advertisement

Figure 7-11: Low calibration value reading
18. Adjust the calibrator to apply the high value (100%) of the signal range. For example, if the
signal range of the external device is 1-5 Vdc, apply 5 Vdc.
19. Click 100% Cal Point. The Enter 100% Calibration Value dialog box displays
20. Observe the value in the Current Reading field. When it stabilizes this value should match or be
close to the signal value from the calibrator (~ 5 Vdc).
21. Type the high range value in the field (1500 for this example) and click OK.
Figure 7-12: User-defined high value
The Reading column updates to reflect the signal value associated with the high value of the range
(Figure
7-13).
1 3 4 | R MC-1 00 | 2 10 5 55 2MN A E
(Figure
7-12).

Advertisement

Table of Contents