Configure The Rmc For 2 Network Mode - ABB RMC-100 User Manual

Remote modular controller
Hide thumbs Also See for RMC-100:
Table of Contents

Advertisement

Figure 4-20: Network communication setup for 1 Network mode
5.
Click Send. The device saves the updated configuration.
6.
Click Restart. A warning displays to confirm.
Figure 4-21: Warning before interface restart
7.
Click Yes.
Click OK.
8.
9.
Verify that the configuration is correct. If DCHP is enabled, ensure the RMC has obtained its
required IP parameters (the IP parameter fields must be automatically populated after the
restart).
10. Ping the device from the WAN or field network. The RMC should reply to the ping from the
network.
11. If connecting another device to the RMC-100 in daisy chain fashion, configure the device with a
unique IP address in the same subnet as the IP address configured on the RMC.
12. Verify that you can reach the connected device by pinging its IP address.
4.7

Configure the RMC for 2 Network mode

The RMC in 2 Network mode separates the two Ethernet interfaces into two logical networks (VLANs).
This mode of operation is displayed as: 2 Networks, in the Mode field on the PCCU Networking tab
screen.