Figure 4-25: Network communication setup for 2 Network mode
Click Send. A message advises you to warm-start or reset the device for the changes to take
5.
effect.
Click Restart. A warning displays to confirm.
6.
Figure 4-26: Warning before interface restart
Click Yes.
7.
8.
Click OK.
9.
Verify that the configuration is correct. If DCHP is enabled, ensure the RMC has obtained its
required IP parameters (the IP parameter fields must be automatically populated after the
restart).
10. Ping the device from the WAN or field network. The RMC should reply to the ping from the
network.
11. If connecting another device to the RMC-100 in daisy chain fashion, configure the device with a
unique IP address in the same subnet as the IP address configured on the RMC.
12. Verify that you can reach the connected device by pinging its IP address.
6 6 | R MC-1 00 | 2 10 55 5 2MN A E