Set up PCCU32 and connect
To configure PCCU32 for TCP/IP communication:
1.
Power on the RMC and the laptop or PC.
2.
Connect the Ethernet cable.
3.
Launch PCCU.
4.
Click Setup on the PCCU32 toolbar menu. The System Setup window displays.
5.
Click TCP/IP.
6.
Type the default IP address (169.254.0.11) into Network ID or IP under Connection Parameters
(Figure
4-8).
Figure 4-8: PCCU setup for local Ethernet communication
Click Close.
7.
Click Entry on the PCCU32 menu bar to connect to the device. The device's Entry screen
8.
displays when a connection is successful.
9.
Configure the controller according to section 4.3.1.