Figure 7-36: Analog inputs 1 and 2 after calibration
4.
Select Factory from the Calibration drop-down list for the appropriate AI
Figure 7-37: Reset AI calibration back to factory defaults
5.
Click Send.
6.
Repeat the calibration procedure in section 7.1.2, Analog input calibration (voltage mode), or
section 7.1.3, Analog input calibration (current mode).
1 5 2 | R MC-1 00 | 2 10 5 55 2MN A E
(Figure
7-37).