Table 2-5: Ethernet Ports - ABB RMC-100 User Manual

Remote modular controller
Hide thumbs Also See for RMC-100:
Table of Contents

Advertisement

ID
Port name
7
COMM
EXPANSION
2.2.2.1
Serial communication ports
The COMM 1 and COMM 2 slots each contain a 40-pin connector to support a hot-swappable serial
communication module
or RS-422) communication between the RMC and external measurement equipment such as pressure
or temperature transmitters, or communication equipment such as radio systems.
DANGER – Serious damage to health / risk to life. Explosion Hazard: Do not connect
or disconnect connectors or their terminations while energized unless the area is known to
be non-hazardous.
Figure 2-7: Hot-swappable communication module
The configured interface type and the distance between the RMC and the connected external device
determine maximum serial communication speed. Supported port speed ranges from 2,400 bps to
115,200 bps.
2.2.2.2
USB port
The USB Type B port provides high-speed serial communications between the RMC and equipment,
host systems or computers with USB interfaces. The port supports local operator access through
PCCU32.
The USB port has two speed modes: full speed and high speed. The RMC automatically negotiates
data transmission rates with the host system.
2.2.2.3
Ethernet ports
The RMC has an embedded managed Ethernet switch. It has two Ethernet ports (E1 and E2) for
communication between the RMC and external devices.
Ethernet ports.

Table 2-5: Ethernet ports

Port name
ETHERNET 1 (E1)
or
ETHERNET 2 (E2)
The RMC supports 2 modes for Ethernet port configuration:
1 8 | R MC-1 00 | 2 10 55 5 2MN A E
Connector
Data transfer rate
type
(port speed)
Proprietary
(Future use)
(Figure
2-7). This module is software-configurable for serial (RS-232, RS-485,
Data transfer rate
(port speed)
10/100 Base-T: 100 Mbps or
10 Mbps full duplex
(supports auto-negotiation
and uses standard or
straight-through Ethernet
cable)
Use (connections)
For future serial communication
modules to expand serial port
capacity
Table 2-5
indicates the uses of the external
Use
Local communications (high-speed
TCP/IP-based local operator interface)
Remote communication using TCP/IP
connections over a network
(management port)
Connect other Totalflow equipment (for
example, XIOs, additional RMCs, flow
computers, etc.):
Connect third-party Ethernet-to-serial
devices.

Advertisement

Table of Contents
loading