Table 2-7: Analog Output Specifications; Table 2-8: Pulse Input Specifications - ABB RMC-100 User Manual

Remote modular controller
Hide thumbs Also See for RMC-100:
Table of Contents

Advertisement

Electrical specification
(each point)
AI input protection Vtvs
2.2.3.2
Analog output
The RMC provides a single (1) analog output. The AO has a voltage-sourcing diode input voltage pin, a
current sinking pin, a current sourcing pin, and a ground pin. The AO can provide 4-20 mA output
through the sink and source pins. Calibrate the AO from the user interface. For specific pinout
information, see section
specifications.

Table 2-7: Analog output specifications

Electrical
specification
(each point)
AO output current
AO sink to source
resistance
AO voltage sourcing
(Vaosrc)
AO current sourcing
(Iaosrc)
AO output resolution
AO output protection
(Vtvs)
2.2.3.3
Pulse input
The RMC provides two pulse inputs (Pulse input, PI). Each PI can accept a variety of input types: 0-5
Vdc TTL input, Open-Collector (Open-Collector, OC), Open-Drain (Open-Drain, OD), or dry switch type
contact. A Schmidt Trigger type gate provides input hysteresis for improved noise protection. Each PI
has a debounce filter configurable from the user interface. For specific pinout information, see section
3.5.5.3 Pulse input
pinouts.
specifications.

Table 2-8: Pulse input specifications

Electrical specification
(each point)
PI open circuit Voc
PI pull up resistance
PI input capacitance in
low pass filter mode
PI input frequency range
with debounce enabled
PI input frequency range
with debounce disabled
PI Vhighmin
PI Vlowmax
PI supported inputs
2.2.3.4
Digital input and output
The six (6) RMC DI/DO support the configurable input or output modes of operation.
The digital input mode handles up to 30 Vdc. The configurable built-in pull-up resistor reads signals
from devices with dry contact and open collector/drain output types.
The digital output mode provides a MOSFET open drain (OD) type output that sinks up to 2 Adc
current.
Description
converter, ADC) resolution for the input
Each AI input has TVS protection, typical V threshold
level to begin conducting.
3.5.5.2 Analog output
pinouts.
Description
Current that the sinking and sourcing pins can
drive
Resistance in the loop on the RMC
Voltage provided at Pin 1
Current range provided at Pin 1
Digital to analog converter (Digital to analog
converter, DAC) resolution for the output
Each AO has onboard TVS protection, typical V
threshold level to begin conducting.
Table
2-8: Pulse input specifications provides the pulse input
Description
PI open circuit voltage
10 kΩ nominal through a diode to input
Capacitance to ground applied to input gate
Frequency range of input (50% duty cycle, OC)
Frequency range of input (50% duty cycle, OC)
High input detection voltage threshold minimum
Low input detection voltage threshold maximum
PI supports: open collector, open drain, dry
switch, 5 V TTL type inputs
Table 2-7
provides the analog output
Value
0 – 24 mA dc
154 Ω
V input to RMC – 0.6 V
(typical)
0-24 mA dc
16-bit resolution
32 Vdc typical
21 05 55 2MN A E | RM C-1 00 | 2 1
Value
32 Vdc typical
Value
5 Vdc
10 kΩ
0.1 µF
0-550 Hz
0-20 kHz
2.4 Vdc (TTL level)
0.8 Vdc (TTL level)
Not applicable