Figure 7-15: Calibration complete message
26. Click OK. Verify that the Entry and Reading values update, and that the Current Value field
displays the calibrated value based on the defined range
IMPORTANT NOTE: After calibration is complete the Current Value field displays range values, not
voltage values.
Figure 7-16: Calibrated AI 1 example (voltage mode)
27. Remain in the calibration screen and keep the calibrator connected to the AI.
28. To verify the calibration, proceed to section 7.1.4, Verify analog input calibration.
1 3 6 | R MC-1 00 | 2 10 5 55 2MN A E
(Figure
7-16).