ABB RMC-100 User Manual page 89

Remote modular controller
Hide thumbs Also See for RMC-100:
Table of Contents

Advertisement

3.
Click the group name on the navigation tree to expand the folder. Then click a Spare group
item The Item Setup tab displays
Figure 5-22: Spare default Item Setup
4.
Click the Name of Display Item field in the Value column and type the display item's new
name. In this example, Flow Rate
5.
Click the field in the Register's Value column. Type the item's Register address. Use the value
obtained in step 2, in this example: 11.7.19.
6.
Type the number of seconds for the item to display into the Display Interval field. The Display
Interval default is zero (0). This example sets the interval to 5 seconds.
7.
Type the unit of measurement for the item's value into the Units field.
(Figure
5-22).
(Figure
5-23)
21 05 55 2MN A E | RM C-1 00 | 8 9