Toshiba GRL100-701B Instruction Manual page 101

Grl100-7**b series. line differential relay
Table of Contents

Advertisement

672
A
673
UVG2 B
674
C
[UVG2EN]
+
"ON"
NON UVGBLK
UVG2_INST_TP
1965
1933
UVG2_BLOCK
Figure 2.9.2.3 UVG Undervoltage Protection (continued)
Setting
The table shows the setting elements necessary for the undervoltage protection and their setting
ranges.
Element
Range
UVS1
5.0 – 150.0 V
TUS1I
0.05– 100.00
TUS1
0.00 – 300.00 s
TUS1R
0.0 – 300.0 s
UVS2
5.0 – 150.0 V
TUS2
0.00 – 300.00 s
VSBLK
5.0 – 20.0 V
UVG1
5.0 – 150.0 V
TUG1I
0.05– 100.00
TUG1
0.00 – 300.00 s
TUG1R
0.0 – 300.0 s
UVG2
5.0 – 150.0 V
TUG2
0.00 – 300.00 s
VGBLK
5.0 – 20.0 V
[UVS1EN]
Off / DT / IDMT
[UVG1EN]
Off / DT / IDMT
[UVS2EN]
Off / On
[UVG2EN]
Off / On
[VBLKEN]
Off / On
TUG2
t
&
&
t
&
&
t
&
&
0.00 - 300.00s
1
(b) UVG2 Undervoltage Protection
Step
Default
Remarks
0.1 V
60.0 V
UVS1 threshold setting
0.01
10.00
UVSI time multiplier setting. Required if [UVS1EN] = IDMT.
0.01 s
0.10 s
UVS1 definite time setting. Required if [UV1EN] = DT.
0.1 s
0.0 s
UVS1 definite time delayed reset.
0.1 V
40.0 V
UV2 threshold setting.
0.01 s
0.10 s
UV2 definite time setting.
0.1 V
10.0 V
Undervoltage block threshold setting.
0.1 V
35.0 V
UVS1 threshold setting
0.01
10.00
UVSI time multiplier setting. Required if [UVS1EN] = IDMT.
0.01 s
0.10 s
UVS1 definite time setting. Required if [UV1EN] = DT.
0.1 s
0.0 s
UVS1 definite time delayed reset.
0.1 V
25.0 V
UV2 threshold setting.
0.01 s
0.10 s
UV2 definite time setting.
0.1 V
10.0 V
Undervoltage block threshold setting.
Off
UVS1 Enable
Off
UVG1 Enable
Off
UVS2 Enable
Off
UVG2 Enable
Off
UV block Enable
 100 
0
≥1
0
≥1
0
≥1
&
&
&
6 F 2 S 0 8 5 0
854
UVG2-A_ALM
855
UVG2-B_ALM
856
UVG2-C_ALM
853
≥ 1
UVG2_ALARM