6.5 Function Test

CAUTION
The function test may cause the output relays to operate including the tripping output relays.
Therefore, the test must be performed with tripping circuits disconnected.
6.5.1
Measuring Element
Measuring element characteristics are realized by software, so it is possible to verify the overall
characteristics by checking representative points.
Operation of the element under test is observed by the binary output signal at monitoring jacks A
or B or by the LED indications above the jacks. In any case, the signal number corresponding to
each element output must be set on the "Logic circuit" screen of the "Test" sub-menu.
When a signal number is entered for the TermA line, the signal is observed at monitoring jack A
and when entered for the TermB line, observed at monitoring jack B.
Note:
CAUTION
Use test equipment with more than 1k Ω of internal impedance when observing the output
signal at the monitoring jacks.
Do not apply an external voltage to the monitoring jacks.
In case of a three-phase element, it is enough to test a representative phase. A-phase is selected
hereafter.
/ 2
L o g
i c c i r c u i t
T e r m
A
(
0 -
T e r m
B
(
0 -
The voltage level at the monitoring jacks is +15V ± 3V for logic level "1" when measured by
an instrument with 10k Ω input impedance, and less than 0.1V for logic level "0".