Toshiba GRL100-701B Instruction Manual page 70

Grl100-7**b series. line differential relay
Table of Contents

Advertisement

Figure 2.3.2.6 shows the scheme logic of the weak infeed trip function. Weak infeed tripping is
executed on condition that a trip permission signal has been received (R1-CR=1, R2-CR=1) for
the POP, and reception of a trip block signal has stopped (R1-CR=0, R2-CR=0) for the UOP, the
undervoltage element UVL (UVLS or UVLG) operates and neither forward overreaching zone 2
or zone 3 nor reverse looking Z4 operates.
R1-CR
1
R2-CR
≥1
1
[TERM]
(+)
"2TERM"
Z4
"Z2"
Z2
[ZONESEL]
Z3
"Z3"
CB-OR
UVL
The undervoltage element responds to three phase-to-phase voltages and three phase-to-ground
voltages. The undervoltage element prevents false weak infeed tripping due to spurious operation
of the channel.
Single-phase tripping or three-phase tripping is also applicable to weak infeed tripping according
to the reclosing mode of the autoreclose function.
The weak infeed trip function can be disabled by the scheme switch [WKIT].
2.3.2.6
Measure for Current Reversal
In response to faults on parallel lines, sequential opening of the circuit breaker may cause a fault
current reversal on healthy lines. This phenomenon may cause false operation of the POP, UOP
and BOP schemes in the worst case. To prevent this, the POP, UOP and BOP are provided with
current reversal logic.
With the parallel line arrangement as shown in Figure 2.3.2.7 (a), suppose that a fault occurs at
time t1 at point F of line L1, A1 trips at time t2 first and then B1 trips at time t3. The direction of
the current that flows in healthy line L2 can be reversed at time t2. That is, the current flows from
terminal B to terminal A as indicated by a solid line in the period from time t1 to t2, and from
terminal A to terminal B as indicated by a broken line in the period from time t2 to t3. This current
reversal phenomenon may occur with the presence of an external looped circuit if not for parallel
lines.
Figure 2.3.2.7 (b) shows a sequence diagram of Z3 and Z4 and the current reversal logic CRL on
healthy line L2 before and after the occurrence of a current reversal. When the current is reversed,
Z3 operation and Z4 reset are seen at terminal A, while reset of Z3 and operation of Z4 are seen at
terminal B. If at this time, Z3 of A2 operates before Z3 of B2 is reset, this may cause false
operation of the POP, UOP and BOP on line L2.
WIT
0
t
≥ 1
250ms
[WKIT]
(+)
"ON"
Figure 2.3.2.6 Weak Infeed Trip Logic
 69 
6 F 2 S 0 8 5 0
876:DISWI_TRIP
&
&
WIT

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Grl100-702bGrl100-711bGrl100-712b

Table of Contents